一起GIS母线开裂故障原因分析

来源:电工电气发布时间:2019-02-19 09:19浏览次数:658
一起GIS母线开裂故障原因分析
 
李玥1,孙涛2
(1 国网兰州供电公司,甘肃 兰州 730050;
2 国网甘肃省电力公司电力科学研究院,甘肃 兰州 730050)
 
    摘 要:针对一起330 kV GIS母线开裂故障,介绍了故障经过及现场检查情况。从GIS母线设备应力计算、伸缩节调节尺寸、故障母线壳体法兰材料检验等方面进行分析,得出此次设备故障原因是设备滑动支撑结构设计不合理,壳体和伸缩节法兰连接的螺栓紧固力矩不均匀,导致壳体法兰圆周方向变形量不同,使法兰局部产生应力集中以及伸缩节选型不当等三方面因素综合作用,引发了母线壳体被拉裂的故障。
    关键词:GIS设备;滑动支撑;伸缩节
    中图分类号:TM595 文献标识码:B 文章编号:1007-3175(2019)02-0035-04
 
Failure Analysis of a Case of Gas Insulated Switchgear Busbar Cracking
 
LI Yue1, SUN Tao2
(1 State Grid Lanzhou Power Supply Company, Lanzhou 730050, China;
2 Electric Power Research Institute of Gansu Province Electric Power Company, Lanzhou 730050, China)
 
    Abstract: Aiming at a case of 330 kV gas insulated switchgear (GIS) busbar cracking failure, this paper introduced the process of failure and on-site inspection conditions and carried out analysis from the aspects of GIS busbar equipment stress calculation, expansion joint regulation size, failure busbar shell flange material examination etc to obtain that this time the cause of equipment failure is due to the unreasonable structure design of equipment sliding support and asymmetry bolt-on force of shell and expansion joint flange connections, so as to lead to the different peripheral direction deflection, to make the flange part stress concentration and to select the improper type of expansion joints etc synthesized action of three factors, which caused the failure of busbar shell cracking.
    Key words: gas insulated switchgear equipment; sliding support; expansion joint
 
参考文献
[1] 李秀卫,王庆玉,毛惠卿,等. 一起组合电器内部绝缘故障综合分析[J]. 高压电器,2012,48(8):99-102.
[2] 崔杨柳,马宏忠,王涛云,等. 基于故障树理论的GIS故障分析[J]. 高压电器,2015,51(7):125-129.
[3] 周义博,万四维,曾宪文,等. 一起220 kV GIS漏气及盆式绝缘子破裂原因分析[J]. 广东电力,2012,25(9):118-121.
[4] 陈强,李庆民,丛浩熹,等. 引入多重边界条件的GIS母线温度分布多场耦合计算及影响因素分析[J]. 电工技术学报,2016,31(17):187-195.
[5] 韩明明,李清泉,刘洪顺,等. 气体绝缘变电站母线结构参数对外壳暂态过电压影响分析[J]. 电工技术学报,2015,30(22):239-246.
[6] 伍斯. 基于ANSYS的避雷针杆的有限元分析[D]. 武汉:湖北工业大学,2012.
[7] 左亚芳.GIS设备运行维护及故障处理[M]. 北京:中国电力出版社,2013.
[8] 罗学琛.SF6气体绝缘全封闭组合电器(GIS)[M]. 北京:中国电力出版社,1999.
[9] 刘泽洪. 气体绝缘金属封闭开关设备(GIS) 质量管理与控制[M]. 北京:中国电力出版社,2011.