一起220 kV线路跳闸的监控信息分析

来源:电工电气发布时间:2020-02-27 13:27浏览次数:989
一起220 kV线路跳闸的监控信息分析
 
赵斌1,王兴涛1,王佳伟1,张亚飞2
(1 国网新疆电力有限公司奎屯供电公司,新疆 奎屯 833200;2 新疆农业大学 电气工程学院,新疆 乌鲁木齐 830002)
 
    摘 要:当变电站端远动装置主通道与备用通道之间在配合上出现问题时,变电站端远动装置会向调度端监控系统上送报文信息,影响调度监控人员对变电站的正常监视。基于某变电站一起220 kV线路跳闸事故时的调度端报文,对报文中存在的备通道补现象进行原因分析,确定为设备硬件原因导致这一现象,经更换远动装置通信板插件后,问题得以解决,为同一类型厂站端自动化系统缺陷处理提供参考。
    关键词:变电站监控系统;线路跳闸;远动装置;主通道;备用通道;报文
    中图分类号:TM726     文献标识码:B     文章编号:1007-3175(2020)02-0043-03
 
Analysis of Monitoring Information of a 220 kV Line Trip
 
ZHAO Bin1, WANG Xing-tao1, WANG Jia-wei1, ZHANG Ya-fei2
(1 Kuitun Electric Power Supply Company of State Grid Xinjiang Power Co., Ltd, Kuitun 833200, China;
2 School of Mechanical and Electrical Engineering, Xinjiang Agricultural University, Urumqi 830002, China)
 
    Abstract: When there is a problem in the coordination between the main channel and the backup channel of the substation terminal remote control device, the substation terminal remote control device will send message information to the dispatching terminal monitoring system, so as to affect the regular substation monitoring of dispatching monitoring personnel. Based on the dispatching terminal message of a 220 kV line trip accident, this paper analyzed the causes of the alternate channel filling phenomenon in the message, making sure that it was the hardware of the device. After the remote control device changed, the problem could be solved, which provides the reference for the same type of factory station automation system defect treatment.
    Key words: substation monitoring system; line tripping; remote control device; main channel; alternate channel; message
 
参考文献
[1] 苗彬. 浅论无人值守变电站的运维管理技术[J].中国新技术新产品,2017(21):77-78.
[2] 翁水,王鹏程. 视频监控系统在无人值守变电站的应用[J]. 科技资讯,2014(36):81-82.
[3] 李茶根,杨晟,曾胜玮,等. 图像智能化分析技术在无人值守变电站安全监控中的应用[J]. 电子技术与软件工程,2016(17):82-83.
[4] 郜勇琴. 变电站综合自动化系统后台信息分析[M].北京:中国电力出版社,2009.
[5] 曹茂昇,高伏英. 电网调度自动化厂站端调试检修[M]. 北京:中国电力出版社,2012.
[6] 潘鹏飞,潘鸣飞,朱亮亮,等. 远动工控机与通道的切换技术[J]. 电网技术,2006,30( S2):407-410.
[7] 夏敏. 变电站远动通道中断的检测方法[J]. 电力安全技术,2014,16(1):46-47.
[8] 袁波. 变电站远动通道通信中断常见故障原因及处理[J]. 科技创新与应用,2015(1):29-30.