(State Grid Shangdong Electric Ultra-High Voltage Company, Jinan 250000, China)
Abstract: As the main operating mechanism of high voltage level, the hydraulic spring operating mechanism is prone to frequent pressure and other failures, and in severe cases, it can cause the circuit breaker to lock, thereby expanding the range of faults. Through the analysis of a 500 kV GIS circuit breaker frequent pressure problem, the on-site inspection of the energy storage control loop is not abnormal, after disassembly,it is found that there are cracks in the inner wall of the working cylinder, resulting in the high pressure area and the low pressure area are connected, and the pressure is frequent. Through macroscopic inspection, metallographic detection, energy spectrum analysis, material review,mechanical performance testing and other methods, the crack causes were deeply studied. Combined with the operation principle of the hydraulic mechanism and the comparison of the working cylinder materials, it was finally determined that the reason for the frequent pressure of the mechanism was the poor processing quality of the working cylinder, and the finished material had relatively many microscopic defects,resulting in axial stress concentration and cracks in the working cylinder. Based on this, the treatment scheme of the same type circuit breaker is given to avoid equipment outage caused by the same problem and ensure the safe operation of the power system.
Key words: circuit breaker; working cylinder; frequent pressure; stress concentration
参考文献
[1] 刘靖羽.GIS 设备现场典型故障及质量管控措施研究分析[J]. 电工电气,2024(1) :65-70.
[2] 国家电网公司人力资源部. 电气设备及运行维护[M] .北京:中国电力出版社,2010.
[3] 梁旭日,麻震烁,李冰玉,等. 一起 500 kV 液压弹簧机构断路器油压低分合闸闭锁故障原因分析[J]. 电气技术,2022,23(9) :93-96.
[4] 杨静文,刘永康,陈双. 特高压液压机构断路器低油压闭锁重合闸分析[J]. 电工电气,2022(7) :74-76.
[5] 李绍武, 李昌静, 孙锦, 等. 一起 110 kV GIS 断路器弹簧操动机构故障分析与处理[J] . 电工电气,2021(11) :74-76.
[6] 刘亚林,吴西博,李威, 等.500 kV 断路器液压弹簧机构频繁打压故障的分析[J] . 高压电器,2022,58(3) :215-220.
[7] 林向宇,连和,庄建煌,等. HMB-4 型液压弹簧机构拒分闸故障的现场检修与防范[J] . 电工电气,2018(11) :72-73.
[8] 王伟,房婷婷. 一起高压断路器液压弹簧操动机构储能回路故障的处置[J]. 电工电气,2016(3) :63-64.
[9] 李清泉,李相栋,冯知海. 一起断路器合闸不到位故障处置流程及原因分析[J]. 电工电气,2023(6) :44-48.
[10] 马佳豪,孙海涛,胡俊,等. 一起 800 kV 断路器液压机构频繁打压故障及分析[J] . 高压电器,2019,55(9) :247-253.
[11] 曾令诚,李新海,林悦德,等. HMB-4 型液压弹簧机构缺陷处理与关键检修策略[J] . 电气应用,2019,38(9) :102-108.
[12] 李锴,徐成西.HMB 型液弹储能机构故障探析及改进措施[J]. 农村电气化,2023(10) :27-30.
[13] 王磊,张恩光,杨建伟. HMB-8.3 型液压弹簧机构频繁打压故障分析与防范[J] . 机械研究与应用,2021,34(5) :178-180.
[14] 羊鑫.HMB 型液压弹簧操作机构电机频繁启动故障原因分析与预防措施[J] . 水电与新能源,2023,37(10) :43-45.
[15] 张卓,李威,刘亚林,等.500 kV 液压弹簧机构频繁打压故障的分析[J]. 高压电器,2023,59(10) :240-246.
[16] 李子由,赵银山.500 kV 开关储能机构异常打压故障分析[J]. 云南电力技术,2023,51(5) :56-60.
[17] 李德武,黄衍臻,张秋强.500 kV HGIS 液压操动机构频繁打压原因分析及对策[J]. 电工技术,2021(22) :89-91.