Suzhou Electric Appliance Research Institute
期刊号: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章检索

首页 >> 文章检索 >> 往年索引

山区风电场风机接地设计探讨

来源:电工电气发布时间:2018-05-09 13:09 浏览次数:662
山区风电场风机接地设计探讨
 
张彦昌,吴之奎,柳羽森,郭群龙,石巍,袁晨
(中南电力设计院,湖北 武汉 430071)
 
    摘 要:风机接地装置作为雷电流泄放主要通道,同时兼工作接地、保护接地,其设计非常重要。但由于山区风电场高土壤电阻率、风机吊装平台面积有限、国内外标准差异等特殊条件,使得山区风电场接地设计较为困难,风机接地网的造价也较高。基于风机接地网的功能,结合现有国内外规范,给出了山区风电场设计的主要原则及思路,供相关人员参考。
    关键词:山区风电场;高土壤电阻率;风机接地网
    中图分类号:TM614     文献标识码:A     文章编号:1007-3175(2018)05-0067-06
 
Discussion on Grounding System Design of Mountain Wind Farm
 
ZHANG Yan-chang, WU Zhi-kui, LIU Yu-sen, GUO Qun-long, SHI Wei, YUAN Chen
(Central Southern Electric Power Design Institute of China, Wuhan 430071, China)
 
    Abstract: As the main channel of lightning flow, the wind turbine grounding device also has the functions of working grounding and safety grounding, so its design is very important. However, due to the special conditions such as high soil resistivity, limited area of wind turbine hoisting platform and the design standard difference at home and abroad, the design of wind farm grounding device in mountainous area was more difficult, and the cost of it was also higher. Based on the function of the wind turbine grounding device and combining with the existing domestic and foreign norms, this paper gave the main principles and ideas of wind turbine grounding device design in mountain areas to provide the references for the related personnel.
    Key words: mountain wind farm; high soil resistivity; wind turbine grounding grid
 
参考文献
[1] GB 51096—2015 风力发电场设计规范[S].
[2] 中国船级社. 风力发电机组规范[S].
[3] IEC 61400-24:2010 Wind turbines-Part24: Lightning protection[S].
[4] IEC 62305:2010 Protection against lightning part1 ~ 4[S].
[5] GB/T 21714—2015 雷电防护[S].
[6] GB/Z 25427—2010 风力发电机组 雷电防护[S].
[7] GB 50169—2016 电气装置安装工程接地装置施工及验收规范[S].
[8] GB/T 50065—2011 交流电气装置的接地设计规范[S].
[9] GB/T 50064—2014 交流电气装置的过电压保护和绝缘配合设计规范[S].
[10] 张彦昌,夏晓东,周才洋,等. 风机与箱变间等电位电缆研究[C]// 中国电力规划设计协会送变电专委会年会论文集,2017.
[11] DL/T 475—2017 接地装置特性参数测量[S].