Suzhou Electric Appliance Research Institute
期刊号: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章检索

首页 >> 文章检索 >> 往年索引

一种快速解环保护及合解环方案

来源:电工电气发布时间:2018-05-09 13:09 浏览次数:597
一种快速解环保护及合解环方案
 
王彦国,余群兵,金震
(南京南瑞继保电气有限公司, 江苏 南京 211102)
 
    摘 要:线路合环运行时,当相邻线路发生故障,且保护或开关拒动后,存在主变误跳、扩大失电范围风险。对合环线路对继电保护的影响进行了分析,针对目前方案带来的级差配合困难、设计回路改动量大、降低保护可靠性等问题提出了一种快速解环保护,避免失电范围扩大,并对某些配网的合环转电操作,提出了一种备自投方案,实现合解环程序化操作,在倒闸失败后自动进行反向合解环,确保重要负荷不失电。
    关键词:合环线路;解环;继电保护
    中图分类号:TM773     文献标识码:A     文章编号:1007-3175(2018)05-0046-05
 
A Kind of Fast Unlink Protection and Loop Closing Scheme
 
WANG Yan-guo, YU Qun-bing, JIN Zhen
(Nari-Relays Electric Co., Ltd, Nanjing 2111 02, China)
 
    Abstract: When the line operating in loop closing mode and the adjacent lines happened to break down, the protection or switch refused to work, so that there were the main transformer breaking by mistake and the power loss range-enlarged risk. This paper analyzed the loop closing line impacts on the relay protection. Aiming at the difficulty of stage difference coordination caused by the existing scheme, the greatly changed design loop and the reduced protection reliability etc problems. This paper proposed a kind of fast unlink protection to avoid the power loss range-enlarged risk. A kind of spare power automatic switching scheme was proposed for the loop closing turning electricity operation of some distribution networks to realize the operation of loop closing line routinization operation. After the back brake broke down, the reverse loop closing started atomically to ensure the important load without losing power.
    Key words: loop closing line; unlink; relay protection
 
参考文献
[1] 张勇,姚建光,俞晓荣,等.具备快速合解环功能的备自投分析[J]. 江苏电机工程,2012,31(1):61-63.
[2] 苑捷. 北京城区配电网合环分析[D]. 北京:华北电力大学,2007.
[3] 张红霞,闫琴,何勇毅,等. 双回线并列运行方式的利弊探讨[J]. 宁夏电力,2009(S1):22-25.
[4] 吴玲,刘勤. 双回线并列运行方式探讨[J]. 四川电力技术,2014,37(1):59-62.
[5] 杨志栋,刘一,张建华,等. 北京10 kV配网合环试验与分析[J]. 中国电力,2006,39(3):66-69.
[6] DL/T 584—2007 3 ~ 110 kV电网继电保护装置运行整定规程[S].
[7] GB/T 14285—2006 继电保护和安全自动装置技术规程[S].
[8] DL/T 684—1999 大型发电机变压器继电保护整定计算原则[S].
[9] 朱景富. 双回线并列运行方式对系统及保护定值的要求[J]. 继电器,2007,35(10):64-65.