泵站二次电压回路及回路电压异常现象分析

来源:电工电气发布时间:2018-10-16 14:16 浏览次数:531
泵站二次电压回路及回路电压异常现象分析
 
张立坚,项德银,任杰
(江苏省灌溉总渠管理处,江苏 淮安 223212)
 
    摘 要:介绍了泵站电力系统的二次电压回路,共性上二次电压的回路结构都可以分解为源头、母线、分支和隔离保护设备,并给出了造成二次电压回路个性的原因。通过对仙人大港泵站双向运行泵站中的二次电压回路的分析,检查出电压互感器V-V 连接方式接地线接错的问题,排除了熔断高压熔丝的隐患。
    关键词:二次电压回路;故障排除;双向运行泵站
    中图分类号:TM77;TV675     文献标识码:B     文章编号:1007-3175(2018)10-0046-03
 
Secondary Voltage Circuit of Pumping Station and Its Voltage Abnormality Analysis
 
ZHANG Li-jian, XIANG De-yin, REN Jie
(General Irrigation Canal Management Department of Jiangsu Province, Huaian 223212, China)
 
    Abstract: Introduction was made to the secondary voltage circuit of power system in the pumping station. The secondary voltage circuit structure from the corner of generality could be divided into source, bus bar, branch and insulation blocking equipment, and the cause of secondary voltage circuitindividuality was given. After the analysis of the secondary voltage circuit of two-way running pump station in Xiaren grand port pump station, the voltage transformer was examined and it was found that the V-Vconnection with grounding wire was wrong, which eliminates the hidden danger of the high pressure fuse.
    Key words: secondary voltage circuit; troubleshooting; two-way running pump station
 