Suzhou Electric Appliance Research Institute
期刊号: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章检索

首页 >> 文章检索 >> 往年索引

大电流固封极柱温升问题分析

来源:电工电气发布时间:2018-11-20 13:20 浏览次数:580
大电流固封极柱温升问题分析
 
王小丽1,杨海锋2,王鹏1,纪江辉1
(1 许继集团有限公司,河南 许昌 461000;2 许昌许继风电科技有限公司,河南 许昌 461000)
 
    摘 要:固封极柱的固封式结构,导致导电体长期通电产生的热量无法散出,温升高引起绝缘失效成为固封极柱绝缘失效的主要原因。从影响温升的主要因素进行分析,提出减小主回路电阻、采用导电性好的材料、增加散热面积等温升解决方案。通过固封极柱温升试验及方案优化,验证了解决方案的可行性,并得出软连接方案在解决大电流固封极柱温升方面更具有优势。
    关键词:固封极柱;主回路电阻;导电材料;散热面积;软连接
    中图分类号:TM561.2     文献标识码:B     文章编号:1007-3175(2018)11-0056-04
 
Analysis of Temperature Rise Problem of Large Current Embedded Pole
 
WANG Xiao-li1, YANG Hai-feng2, WANG Peng1, JI Jiang-hui1
(1 XJ Group Corporation, Xuchang 461000, China; 2 XJ Wind Power Technology Co., Ltd, Xuchang 461000, China)
 
    Abstract: The solid sealing structure of embedded pole leads to not dissipating the heat generated by the long-term conduction of the conductor. The high temperature rising is the main reason for the insulation failure of embedded pole. Based on the analysis of the main factors influencing on the temperature rising, this paper proposed the solutions such as reducing the circuit resistance, using conductive materials with good conductivity and increasing the heat radiation area. Through the temperature rising test and scheme optimization of the solid sealed pole, the feasibility of the scheme was verified.It is concluded that the high-current solid-blocking pole soft connection scheme has more advantages in solving the temperature rising problems.
    Key words: embedded pole; main circuit resistance; conductive materials; heat radiation area; soft connection
 
参考文献
[1] 纪江辉,张杰,王小丽,等.40.5 kV固封极柱的设计及工艺优化[J]. 电工电气,2016(12):52-55.
[2] 吴建红,葛乐矣,王福润,等. 中压固体绝缘环氧树脂APG制造新工艺[J]. 电工电气,2015(1):47-50.
[3] 中国国家标准化管理委员会. 高压开关设备和控制设备标准的共用技术要求:GB/T 11022—2011[S]. 北京:中国标准出版社,2012:22-23.
[4] 黎斌.SF6高压电器设计[M]. 3 版. 北京:机械工业出版社,2010.
[5] 国家能源局. 高压开关设备和控制设备标准的共用技术要求:DL/T 593—2016[S]. 北京:中国电力出版社,2016:46.
[6] 张正周,宋新峰,独田娃,等. 弹簧触头设计Ⅲ [J]. 高压电器,2011,47(5):87-91.