高压开关操作引起瞬态电磁干扰的实测分析

来源:电工电气发布时间:2016-03-11 12:11 浏览次数:9

高压开关操作引起瞬态电磁干扰的实测分析 

钱佳斌,王立辉,魏广进 
东南大学 仪器科学与工程学院,江苏 南京 210096 
 

摘 要:为研究高压开关重击穿过程的发生规律,分析隔离开关和断路器操作产生电磁骚扰的特性,对500kV变电站开关操作过程中导致二次回路的电磁干扰进行现场测量,并对开关操作产生的骚扰电压进行时域和频域特性分析,确定骚扰等级及主频范围。测量结果表明,就地汇控柜内二次设备端口骚扰电压幅值达到320V,频率分布集中在45.83MHz之内。断路器操作时端口骚扰电压有较大的幅值水平,尤其是断路器分闸-合闸-分闸操作时端口骚扰电压在幅值、微脉冲持续时间和上升沿上,相对于隔离开关操作有更为严重的情况出现。
关键词:高压开关操作;电磁骚扰;时频特性;端口骚扰电压
中图分类号:TM561;TM564.1 文献标识码:A 文章编号:1007-3175(2015)10-0046-05


Actual Measurement Analysis of Transient Electromagnetic Interference Caused by High-Voltage Switch Operation 

QIAN Jia-bin, WANG Li-hui, WEI Guang-jin 
School of Instrument Science and Engineering, Southeast University, Nanjing 210096, China 
 

Abstract: In order to research the outbreak regularity of the repeated break down process, analysis was made to the characteristics of the electromagnetic disturbance caused by the isolation switch and circuit breaker operation. The electromagnetic disturbance of secondary circuits caused by the switching operation was measured in the field, when 500kV substation just put into operation. This paper analyzed the time and frequency characteristics of disturbance voltage in the transient process and determined the disturbance level and the range of dominant frequency. Measurement results show that the maximum disturbance voltage on the ports of secondary equipment in control cabinets is 320V, and the disturbance frequency is focus on the range of 45.83MHz. There is considerable disturbance voltage amplitude during circuit breaker closing operations. Especially, there is more serious situation on the amplitude, micro-pulse duration and rising time of the disturbance voltage during circuit breaker under opening-closing-opening operations.
Key words: high-voltage switch operation; electromagnetic interference; time-frequency characteristic; port disturbance voltage


参考文献
[1] De Abreu Silveira C, Da Costa C A, Da Costa e Silva R, et al.Electromagnetic Environment Measurement under Steady-State Conditions in Utility Substations[C]//Transmission & Distribution Conference and Exposition,2006.
[2] 杜林,唐启尧,陈辉.三峡电站GIS快速暂态过电压现场试验及分析[J].高电压技术,2009,35(7):1743-1747.
[3] 张卫东,陈沛龙,陈维江,等.特高压GIS变电站VFTO对二次电缆骚扰电压的实测与仿真[J].中国电机工程学报,2013,33(16):187-196.
[4] 李志兵,陈维江,王浩,等.特高压交流试验示范工程GIS隔离开关带电操作试验[J].高电压技术,2012,38(6):1436-1444.
[5] 卢斌先,王泽忠,李成榕,等.500kV变电站开关操作瞬态电场测量与研究[J].中国电机工程学报,2004,24(4):133-138.
[6] 李小建,钟尧,王任,等.超高压系统隔离开关操作电磁骚扰的时频特性[J].高电压技术,2012,38(11):2889-2897.
[7] 张禹芳,宋继明.500kV交流输变电工程启动调试中断路器分合分试验的探讨[J].电网技术,2007,31(17):7-10.