架空输电线路110 kV复合绝缘子闪络故障原因分析

来源:电工电气发布时间:2019-06-13 13:13 浏览次数:621
架空输电线路110 kV复合绝缘子闪络故障原因分析
 
陈宇飞1,李玉超2,张耀男3,常彬4,陈泓5,韩宏伟4
(1 北京国电龙源环保工程有限公司,北京 100039;
2 国网中卫供电公司,宁夏 中卫 755000;3 国网银川供电公司,宁夏 银川 750002;
4 宁夏电力能源科技有限公司,宁夏 银川 750002;5 国网宁夏电力有限公司,宁夏 银川 750001)
 
    摘 要:针对西北某地区110 kV架空输电线路复合绝缘子闪络故障跳闸事件,对闪络后复合绝缘子进行电气性能、尺寸等方面进行试验,分析了故障发生时天气情况、地理环境等,得出故障原因为雨水造成的复合绝缘子湿闪络,并提出了针对性预防措施及处理建议,防止类似故障再次发生。
    关键词:架空输电线路;复合绝缘子;闪络故障
    中图分类号:TM216     文献标识码:B     文章编号:1007-3175(2019)06-0034-03
 
Cause Analysis of Flashover Fault of 110 kV Composite Insulator on Overhead Transmission Line
 
CHEN Yu-fei1, LI Yu-chao2, ZHANG Yao-nan3, CHANG Bin4, CHEN Hong5, HAN Hong-wei4
(1 Beijing Guodian Longyuan Environmental Protection Engineering Co., Ltd, Beijing 100039, China;
2 State Grid Zhongwei Power Supply Company, Zhongwei 755000, China; 3 State Grid Yinchuan Power Supply Company, Yinchuan 750002, China;
4 Ningxia Power Energy Technology Co., Ltd, Yinchuan 750002, China; 5 State Grid Ningxia Electric Power Co., Ltd, Yinchuan 750001, China)
 
    Abstract: In allusion to the flashover fault tripping events of composite insulators in 110 kV overhead transmission lines in a certain area of northwest region, the electrical performance and size of composite insulators after the flashover were carried out tests.This paper analyzed the weather situation and geographical conditions when the faults happened.It is concluded that the cause of the fault is the wet flashover of composite insulators caused by rainwater, and the preventive measures and treatment suggestions are put forward to prevent similar failures from happening again.
    Key words: overhead transmission lines; composite insulators; flashover fault
 
参考文献
[1] 王涛,孙黎新,吕咸文,等.110 kV线路硅橡胶复合绝缘子闪络故障点的查找[J]. 电工技术,2011(2):63-64.
[2] 吴经锋, 邱毓昌, 张建荣, 等. 运行中复合绝缘子闪络特性抽样试验分析[J]. 电瓷避雷器,2002(1):10-12.
[3] 盛慧慧,杨静. 一起罕见的220 kV架空线路雷击故障跳闸分析[J]. 电力科学与工程,2011,27(5):56-59.
[4] 中国电器工业协会. 标称电压高于1 000 V的架空线路用复合绝缘子串元件 第2 部分:尺寸与特性:GB/T21421.2—2014[S]. 北京:中国标准出版社,2014:1-3.
[5] 中国电器工业协会. 标称电压高于1 000 V的交流架空线路用复合绝缘子—定义、试验方法及验收准则:GB/T 19519—2014[S]. 北京:中国标准出版社,2014:14-15.