Suzhou Electric Appliance Research Institute
期刊号: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章检索

首页 >> 文章检索 >> 往年索引

智能变电站备自投装置误动分析及改进措施

来源:电工电气发布时间:2020-11-19 14:19 浏览次数:571
智能变电站备自投装置误动分析及改进措施
 
吴勇海
(国网福建省电力有限公司龙岩供电公司,福建 龙岩 364000)
 
    摘 要:分析了一座110 kV智能变电站在母线电压互感器PT 及一条110 kV线路转检修过程中,110 kV备自投装置动作后,未合上备用线路开关,造成全站短时失压的事故。通过对现场备自投装置动作报文、开入量SOE变位及监控后台报文分析,并查阅该110 kV备自投装置说明书,得到备自投装置在联切线路转检修时逻辑存在问题——联切线路的跳位取的是操作箱的TWJ,断开操作电源时TWJ 复归。根据影响110 kV备自投正确动作的不同原因提出:一是增加联切线路检修时对应的线路相对应的检修开入压板;二是110 kV进线备自投的两条互备线路及母线PT,三者其中之一转检修,也同时将备自投装置退出,以防备自投装置误动。
    关键词:智能变电站;备自投装置;误动;改进措施
    中图分类号:TM63     文献标识码:B     文章编号:1007-3175(2020)11-0049-04
 
Analysis and Improvement Measures of an Incorrect Operation of the Reserve
Power Source Automatic Connection Devices in Smart Substation
 
WU Yong-hai
(Longyan Power Supply Company, State Grid Fujian Electric Power Company, Longyan 364000, China)
 
    Abstract: In this paper, analysis an 110 kV smart substation in the bus voltage transformer PT and an 110 kV line in the process of overhaul, after the 110 kV reserve power source automatic connection devices(RPSACDs)is activated, the backup line switch is not closed, causing a short-term voltage loss of the whole station.By analyzing the operation messages of the on-site RPSACDs, the position of the input SOE and monitoring the background message, and consulting the 110 kV RPSACDs manual, it is found that the RPSACDs has logic problems when the combined switching line is transferred for maintenance— —The jump position of the combined circuit is the TWJ of the operation box, and the TWJ will reset when the operating power is disconnected.According to the different reasons that affect the correct operation of 110 kV standby automatic switching, the following is proposed: First, increase the maintenance opening of the corresponding line during the maintenance of the combined line; the second is the two mutual backup lines and busbar PT of 110 kV incoming line and automatic switching.One of the three is transferred to overhaul, and the automatic RPSACDs is also withdrawn to prevent the RPSACDs from malfunctioning.
    Key words: smart substation; reserve power source automatic connection devices; incorrect operation; improvement measures
 
参考文献
[1] 林桂辉,甘德树,吴海雄,等. 考虑备自投动作的电网运行事故等级预判方法研究及系统开发[J]. 电气自动化,2018,40(3):78-80.
[2] 毛宇晗,张焰,苏运. 多电压等级配电网备用电源自动投切装置的优化配置方法[J]. 电力自动化设备,2018,38(6):72-78.
[3] 马力,宋庭会,库永恒. 防止母线PT断线引起备自投不正确动作的研究与改进[J]. 继电器,2008,36(2):79-81.
[4] 张健. 不完全扩大内桥接线下智能站备自投方案探讨[J]. 安徽电气工程职业技术学院学报,2019,24(3):74-77.
[5] 孙立新,孙华. 一次备自投装置误动的思考[J].电力系统保护与控制,2009,37(21):134-137.
[6] 曹伟杰,王誉娇,陶天祎,等. 智能站备自投装置误动分析[J]. 电气技术,2019(5):90-91.
[7] 邹德虎,徐希,闪鑫. 基于集中校核与分散控制的备自投系统[J]. 电力系统保护与控制,2017,45(21):140-146.
[8] 仲雅霓,姚成,郄朝辉,等. 智能变电站基于站控层GOOSE输入输出的备自投装置研制[J]. 电气自动化,2016,38(1):62-64.
[9] 杨忠礼,赵慧光,张光衡. 影响备自投正确动作原因分析[J]. 电力系统保护与控制,2008,36(21):97-99.