环氧树脂绝缘站用变压器局部异常发热检测分析与消除

来源:电工电气发布时间:2021-11-19 08:19 浏览次数:384

环氧树脂绝缘站用变压器局部异常发热检测分析与消除

刘泊辰1, 郝洪民1, 苗军1, 咸日常2, 陈蕾2, 郭洋2, 李佳琪2
(1 国网山东省电力公司淄博供电公司,山东 淄博 255000;
2 山东理工大学 电气与电子工程学院,山东 淄博 255000)
 
    摘 要:由于站用变压器长期运行在高电压、高场强和负载电流条件下,所处环境工况复杂,其绝缘性能失效事件时有发生。通过红外热像仪测温、长焦相机拍照的带电检测方法,结合离线电气试验,分析了一起 35 kV 干式绝缘站用变压器因局部机械受损、运行环境湿度大,从而导致其绕组环氧树脂绝缘性能下降并发生沿面放电,进而引起局部异常发热的案例,并介绍了修复方案和预防措施,为保障站用变压器的安全稳定运行和维修试验提供了参考。
    关键词:站用变压器;带电检测;绝缘性能;沿面放电;异常发热
    中图分类号:TM401     文献标识码:B    文章编号:1007-3175(2021)11-0047-04
 
Detection Analysis and Elimination of Local Abnormal Heating of Epoxy
Resin Insulated Station Transformer
 
LIU Bo-chen1, HAO Hong-min1, MIAO Jun1, XIAN Ri-chang2, CHEN Lei2, GUO Yang2, LI Jia-qi2
(1 State Grid Shandong Electric Power Company Zibo Power Supply Company, Zibo 255000, China;
2 School of Electrical and Electronic Engineering, Shandong University of Technology, Zibo 255000, China)
 
    Abstract: The insulation failure event of station transformers is a frequent occurrence due to the long-term operation of the transformers for power stations under high voltage and high electric stress, overload current, and complex working conditions. This paper analyzed a typical case a 35 kV dry-type insulation substation transformer has a local heating phenomenon. The phenomenon is caused by the insulation of epoxy resin winding decreasing and creeping discharge, which was triggered by the mechanical fault and high environmental relative humidity.This article introduces the repair plan and preventive measures, which could provide a reference for ensuring the safe and stable operation and maintenance test of the transformers for power stations.
    Key words: station transformer; live detection; insulation performance; creeping discharge; abnormal heating
 
参考文献
[1] 张鹏,齐波,李成榕,等.电力变压器油中溶解气体特性影响因素的量化分析[J].中国电机工程学报,2021,41(10) :3620-3631.
[2] 陈蕾,咸日常,郑春旭,等.系统单相接地故障下接地变压器的运行特性分析[J].电力系统保护与控制,2021,49(12) :56-64.
[3] 秦川,李景灿,范镇南.35 kV 站用变压器爆炸事故分析[J].变压器,2021,58(2) :85-87.
[4] 付轶,刘涛,梁仕斌,等.35 kV 站用变压器直流电阻异常分析[J].云南电力技术,2019,47(2) :39-42.
[5] 端木林楠,赵习静,蔡巍,等.某 220 kV 变电站 35 kV 站用变压器爆炸事故分析与处理[J].高压电器,2015,51(12) :174-178.
[6] 谢耀恒,雷红才,黄海波,等.环氧树脂湿热老化过程分子模拟仿真研究[J].绝缘材料,2019,52(9) :70-77.
[7] 杨敏,王新,童小忠,等.环氧树脂/Al2O3 纳米复合材料直流电树枝及局部放电特性研究[J].绝缘材料,2021,54(6) :49-55.
[8] 池明赫,李毅恒,罗青林,等.运行环境对换流变压器油纸绝缘电场分布的影响[J].电机与控制学报,2021,25(5) :71-79.