凝露对变频器的影响分析及预防措施

来源:电工电气发布时间:2016-03-14 10:14 浏览次数:9

凝露对变频器的影响分析及预防措施 

孙海军

浙江大唐乌沙山发电有限责任公司,浙江 宁波 315722 
 

摘 要:针对某沿海电厂一起变频器整流单元短路故障事故,分析得出母线铜排凝露的产生是引起本次变频器短路的主要原因,讨论了凝露对变频器的影响机理,给出了预防凝露的措施,指出只要保持变频器柜体内部温度始终高于外部环境温度,即可防止变频器柜体内部发生凝露,降低突发事故风险。
关键词:凝露;变频器;故障;预防措施
中图分类号:TN773 文献标识码:A 文章编号:1007-3175(2015)02-0035-03


Analysis and Precaution of Condensation Effects on Inverter 

SUN Hai-jun 
Zhejiang Datang Wushashan Power Co., Ltd, Ningbo 315722, China 
 

Abstract: Based on the short-circuit fault accident of a inverter rectifier unit in a coastal power plant, this paper analyzed that the condensation generated by bus bar copper bar was the main reason to cause inverter short circuit this time, and discussed the condensation influence mechanism to inverter, providing measures to prevent condensation. It is pointed out that the inverter cabinet internal condensation would be prevented, only if the internal temperature of inverter cabinet is kept higher than external environment temperature, which will reduce the accident risk.
Key words: condensation; inverter; failure; precautions


参考文献
[1] 周军,周文越.开关柜防凝露控制技术浅谈[J].科技创新导报,2010(1):57. 
[2] 曹国荣,赵燕峰.变频器的除湿防凝露研究[J].变频器世界,2011(6):129-132.