10 kV户外柱上断路器容量性能试验的关键点及控制措施

来源:电工电气发布时间:2022-09-26 14:26 浏览次数:232

10 kV户外柱上断路器容量性能试验的关键点及控制措施

李啸,李钊,刘德宇,顾晓贺
(常州博瑞电力自动化设备有限公司,江苏 常州 213025)
 
    摘 要:对带隔离开关的户外柱上断路器而言,容量性能试验要求为过程中不能发生真空灭弧室触头和隔离开关触头打火或熔焊现象。从真空灭弧室触头的选型、断路器机械特性参数的调试、隔离开关触头形式的选择、隔离开关触头压力的调校四个方面,通过多次容量性能试验的摸底测试,分别提出了真空灭弧室触头采用杯状纵磁结构触头,机械特性调试参数满足灭弧室的技术参数,隔离开关触头采用线接触形式,及隔离开关触头压力值控制在(185±25) N 的技术关键点,并对真空灭弧室的生产和隔离开关触头的压力值也提出了控制措施,为柱上断路器的器件选型、关键工艺控制、质量管控等提供了参考。
    关键词: 柱上断路器;隔离开关;容量性能试验;特性参数;触头压力
    中图分类号:TM561     文献标识码:B     文章编号:1007-3175(2022)09-0046-05
 
Key Points and Control Measures of Capacity Performance Test of the
10 kV Outdoor Pole-Mounted Circuit Breaker
 
LI Xiao, LI Zhao, LIU De-yu, GU Xiao-he
(Changzhou Boil Electric Power Automation Equipments Co., Ltd, Changzhou 213025, China)
 
    Abstract: For an outdoor pole-mounted circuit breaker with isolating switch, test requirements are that the contact of vacuum interrupter and isolating switch cannot be ignited or fused.This paper discussed the selection of vacuum interrupter contacts, the adjustment of the mechanical characteristic parameter of the circuit breaker, the contact types of the disconnector selection, and the adjustment of the contact pressure of the disconnector. Based on the capacity performance test this study proposed four suggestions: the contact of vacuum interrupter should use cupshaped longitudinal magnetic structure, the adjustment parameters of mechanical characteristics have to meet the technical parameters of arc interrupter, the isolating switch uses the line contact form, and the (185±25) N is the technical point of the contact pressure of isolating switch.In addition, this paper proposed the control measures for the production of the vacuum interrupter and the pressure value of the contact of the isolating switch. It provides a reference for the component selection of the pole-mounted circuit breaker, the key-process control and the quality control of the pole-mounted circuit breaker, etc.
    Key words: pole-mounted circuit breaker; isolating switch; capacity performance test; characteristic parameter; contact pressure
 
参考文献
[1] 李静,谷禹.10 kV 户外柱上断路器短路开断试验中一体式隔离开关触头烧蚀影响分析[J] . 设备研制与应用,2017,34(12):66-70.
[2] 全国高压开关设备标准化技术委员会. 高压交流断路器:GB 1984—2014[S]. 北京:中国标准出版社,2014:43.
[3] 全国高压开关设备标准化技术委员会. 高压交流隔离开关和接地开关:GB 1985—2014[S] . 北京:中国标准出版社,2014:20-22.
[4] 李刚,高享想,刘浩军,等. 高压交流断路器大容量短路开断与关合试验技术[J] . 高压电器,2018,54(2):68-75.
[5] 盛民学,王志清. 户外高压隔离开关常见故障的原因分析处理[J] . 高压电器,2010,46(10):93-96.
[6] 胡红光. 隔离开关触头结构与发热原因分析[J] .高电压技术,2001,27(5):72-75.
[7] 宋辉,刘顺新. 真空开关电弧的研究分析[J] . 电气制造,2013(10):28-31.
[8] 游一民,欧阳振国,马平,等. 影响真空断路器关合时触头熔焊的另一重要因素[J] . 高压电器,2014,50(8):53-56.
[9] 姜生,李世民,王继元. 真空断路器机械特性的探讨[J]. 高压电器,2002,38(4):61-64.
[10] 沈佩琦,李为民,周友东.10 kV 户外柱上开关存在的问题及对策[J]. 高压电器,2017,53(4):211-214.