一起10 kV箱式柱上断路器击穿故障分析及处理
李啸,赵高超,惠杰,袁玉国
(常州博瑞电力自动化设备有限公司,江苏 常州 213025)
摘 要:针对某架空线路上的断路器故障导致保护跳闸动作,重合闸未能消除异常,现场发现 B 相绝缘套管桩头有明显烧蚀发黑的现象,对下杆的故障断路器进行绝缘电阻和套管端子水平度试验,明确了故障部位;查看馈线终端动作报告,拆解并查看箱内元器件情况,对绝缘套管开展 X 光透视和电场仿真分析,得出故障原因为 B 相带电主回路贯穿受损的环氧树脂层对壳体产生击穿放电,沿面闪络后引发单相接地故障;对同批次的套管进行机械和电气性能测试,排除套管本身缺陷问题,明确套管开裂原因为其受到瞬间碰撞或人为搬抬时的外力作用导致环氧树脂层受内应力并出现肉眼不可见的裂纹。提出了加强环氧树脂浇注的生产工艺,适时开展工频耐压试验等防范措施。
关键词: 断路器;绝缘套管;击穿;环氧树脂;故障分析
中图分类号:TM561 文献标识码:B 文章编号:1007-3175(2023)12-0045-04
Analysis and Treatment of a Breakdown Fault Happening to
10 kV Box-Mode Column Circuit Breaker
LI Xiao, ZHAO Gao-chao, HUI Jie, YUAN Yu-guo
(Changzhou Boil Electric Power Automation Equipments Co., Ltd, Changzhou 213025, China)
Abstract: A circuit breaker fault occurring to the overhead lines causes trip protection, the reclosing breaker failed to eliminate the abnormality,and the B-phase insulation sleeve pile head is found to have obvious ablation and blackening phenomenon. Through carrying out the insulation resistance test and bushing terminal levelness test to the fault circuit breaker of the lower pole, the fault part is located. Then,the paper views the feeder terminal action report, disassembles and checks the components in the box, and carries out X-ray fluoroscopy and electric field simulation analysis on the insulation sleeve. It finds out that B-phase charged main circuit penetrates the damaged epoxy resin layer, which produces disruptive discharge to the shell and leads to the single-phase grounding fault after the surface flashover. The mechanical and electric performance tests have been taken to the same batch of sleeves to eliminate their own defects, and the reason for sleeve cracking is the external force produced by instantaneous collision or artificial lifting causes the epoxy resin layer to bear internal stress to generate cracks invisible to the naked eye. Therefore, the paper puts forward preventive measures such as strengthening the production process of epoxy resin pouring and carrying out power-frequency voltage-withstand test in time.
Key words: circuit breaker; insulation sleeve; breakdown; epoxy resin; fault analysis
参考文献
[1] 沈佩琦,李为民,周友东.10 kV 户外柱上开关存在的问题及对策[J] . 高压电器,2017,53(4) :211-214.
[2] 郝放,滕振业. 绝缘套管放电原因分析与对策[J].科技视界,2012(12) :59.
[3] 张忠华.6 kV 真空断路器的故障分析及解决措施[J].电子技术与软件工程,2017(14) :224.
[4] 蒲军. 简易变电站的10 kV 线路保护越级跳闸故障分析[J]. 电气技术,2021,22(4) :73-77.
[5] 李通,李顺尧,黎浩钧. 一起10 kV 柱上真空断路器故障的解体分析[J] . 电工电气,2021(3) :70-71.
[6] 中国电器工业协会. 高压交流断路器:GB 1984—2014[S]. 北京:中国标准出版社,2014 :52-53.
[7] 乌小茜,刘锋,刘瑞,等.6 kV 高压开关柜绝缘套管击穿原因分析及处理[J] . 内蒙古电力技术,2014,32(6) :117-119.