35 kV绝缘管型母线接地故障分析与防范措施

来源:电工电气发布时间:2026-10-22 11:22 浏览次数:13

35 kV绝缘管型母线接地故障分析与防范措施

许洪华,张鹏,赵阳,李喆,袁杰
(中国石油天然气股份有限公司广西石化分公司,广西 钦州 535008)

    摘 要 :绝缘管型母线是电力输变电系统中用于导体连接的关键设备,但若管母存在绝缘缺陷、设备工艺缺陷、环境因素及运维不当等原因,将会导致管母绝缘击穿,进而造成大面积停电事故。以一起220 kV 变电站主变 35 kV 侧绝缘管型母线接地短路故障为研究对象,系统分析了故障时序、保护动作逻辑及放电特征,并揭示了绝缘管型母线由隐性缺陷引发的绝缘渐进劣化,最终导致击穿的故障机理。为防范此类故障,提出了融合局部放电在线监测、介质损耗实时检测、绝缘电阻趋势分析及温度监控的多参数综合诊断方案,并结合分级维护策略,增强缺陷早期识别与风险管控能力,为高压配电系统中绝缘管型母线的运行维护与故障预防提供了参考。
    关键词 : 绝缘管型母线 ;绝缘击穿 ;接地短路故障 ;局部放电 ;介质损耗 ;绝缘电阻
    中图分类号 :TM645.1+1     文献标识码 :B     文章编号 :2097-6623(2026)10-0045-06


35 kV Insulated Tubular Busbar Grounding Fault Analysis and
Prevention Measures

XU Hong-hua, ZHANG Peng, ZHAO Yang, LI Zhe, YUAN Jie
( PetroChina Guangxi Petrochemical Company, Qinzhou 535008, China)


    Abstract: Insulated tubular busbars are key equipment for conductor connection in power transmission and substation systems. However,insulation defects, manufacturing process flaws, adverse environmental conditions and improper operation and maintenance can cause insulation breakdown of tubular busbars, further resulting in large-scale power outages. Taking a grounding short-circuit fault of the insulated tubular busbar on the 35 kV side of the main transformer in a 220 kV substation as the research object, this paper systematically analyzes the fault time sequence, protection operation logic and discharge characteristics, and reveals the fault mechanism of insulated tubular busbars, in which latent defects induce gradual insulation deterioration and eventually lead to insulation breakdown. To prevent such faults, a multi-parameter comprehensive diagnosis scheme integrating online partial discharge monitoring, real-time dielectric loss detection, insulation resistance trend analysis and temperature monitoring is proposed. Combined with a hierarchical maintenance strategy, the scheme improves the capabilities of early defect identification and risk control, providing a reference for the operation, maintenance and fault prevention of insulated tubular busbars in high-voltage power distribution systems.
    Key words: insulated tubular busbar; insulation breakdown; grounding short-circuit fault; partial discharge; dielectric loss; insulation resistance

参考文献
[1] 傅利成,赵旭州,周刚,等 . 一起 220 kV 变电站低压侧绝缘管母 A 相异常事故的分析与思考 [J]. 电气开关,2024,62(6) :112-116.
[2] 商旺旺,付杰 . 盐穴储能电站绝缘铜管型母线安装技术研究 [J]. 电工电气,2025(3) :64-68.
[3] 李俊恒 . 一起风电场固体绝缘管母故障的综合分析 [J].电工技术,2024(7) :188-191.
[4] Tang Liezheng,Ruan Jiangjun,Chen Rou,et al.Conductor temperature monitoring for the fully insulated busbar prefabricated joint considering contact resistance[J].IET Generation,Transmission & Distribution, 2023, 17(1) :91-101.
[5] 闻煜峰, 魏泽民, 王耀升, 等 . 一起主变全绝缘管型母线异常事件分析 [J]. 电力安全技术,2023,25(9) :27-30.
[6] 曹雨军,朱红亮,夏芳敏,等 .110 kV 冷绝缘超导电缆本体优化设计 [J]. 电工电气,2023(5) :24-28.
[7] Mhatre S,Thaokar R.Electrocoalescence in nonuniform electric fields :an experimental study[J].Chemical Engineering and Processing:Process Intensification,2015,96 :28-38.
[8] Bian H H,Guo Z Y,Zhou C G,et al.Research on orderly charge and discharge strategy of EV based on QPSO algorithm[J].IEEE Access,2022,10 :66430-66448.
[9] 于克锐, 陈驰, 关雨新, 等 . 高压电缆在电压极性反转过程中的空间电荷行为研究 [J]. 电工电气,2024(4) :54-59.
[10] 任志勇,张天旭 . 一起 110 kV 变压器内部放电故障分析 [J]. 电工电气,2024(1) :71-73.
[11] 郭述志,段琰璞,杨庆学 . 核电厂 500 kV 主变压器局部放电异常分析 [J]. 电工电气,2021(1) :43-46.
[12] 宋诚,李文志,鲁杨,等 . 非接触式密集型母线槽测温系统研究 [J]. 电工电气,2022(3) :42-45.