Suzhou Electric Appliance Research Institute
期刊号: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章检索

首页 >> 文章检索 >> 往年索引

杭州地区输电线路雷击故障原因及对策

来源:电工电气发布时间:2016-04-06 09:06 浏览次数:22

杭州地区输电线路雷击故障原因及对策 

杨先进,胡伟,费敏 
国网杭州供电公司,浙江 杭州 310009 
 

摘 要:分析了杭州地区110 ~ 500 kV 输电线路雷击跳闸原因,并根据该地区雷电活动的特点制定了相应的防雷改造对策,通过采用“改造接地电阻为主,加装避雷器为辅”的防雷措施,大幅度提高杆塔的反击耐雷水平,有效防止线路绕击,降低了线路雷击跳闸率。
关键词:输电线路;雷击;原因;对策
中图分类号:TM862 文献标识码:B 文章编号:1007-3175(2014)02-0041-03


Transmission Line Lightning Fault Causes and Countermeasures in Hangzhou Area 

YANG Xian-jin, HU Wei, FEI Min 
Hangzhou Power Supply Company of State Grid, Hangzhou 310009, China 
 

Abstract: Analysis was made to 11 0~500 kV transmission line lightning tripping causes in Hangzhou area and according to the features of the area lightning activities, this paper laid down the corresponding anti-lightning reform countermeasures. Via adoption of anti-lightning measures as reforming grounding resistance as the main; additionally installing arrestors as the assistance, the anti-lighting level of pole tower was greatly lifted, which effectively prevents lines from winding lighting, reducing line lighting tripping rate.
        Key words: transmission line; lightning; cause; countermeasure


参考文献
[1] DL/T 620—1997 交流电气装置的过电压保护和绝缘配合[S].
[2] 金祖山,胡文堂,龚坚刚,等. 浙江电网降低高压输电线路雷击跳闸率的措施分析[ J ] . 浙江电力,2010,29(11):1-5.
[3] 周远翔,鲁斌,燕福龙,等. 山区复杂地形输电线路绕击跳闸率的研究[ J ] . 高电压技术,2007,33(6):45-49.
[4] 金祖山,吴健儿.220 k V 同塔双回输电线路雷击跳闸原因分析[J]. 浙江电力,2009,28(1):51-53.