基于频率监测网中广域电压相角的区域间振荡分析

来源:电工电气发布时间:2016-04-06 09:06 浏览次数:12

基于频率监测网中广域电压相角的区域间振荡分析 

李冰1,吴振跃1,刘奕路2,肖登明1,焦俊韬1


1 上海交通大学 电气工程系,上海 200030;
2 田纳西大学 电气工程与计算机工程系,田纳西 诺克思维尔 37901
 
 

摘 要:区域间振荡会严重影响系统的正常运行,一旦线路发生连锁故障,将引发更大的系统扰动。通过频率监测网捕捉到了美国东部互联电力网发生的6 例典型的区域间振荡现象并使用矩阵束方法对电压相角相对值多路数据进行了模态分析,计算了相应的振型参数,提出了每一个振荡现象案例的主模的振型,分析其结果并给出了东部互联电网的区域间振型的分布情况。
关键词:区域间振荡;矩阵束;振型;广域监测系统 中图分类号:TM764.1;TM935 文献标识码:A 文章编号:1007-3175(2014)02-0011-06


Inter-Area Oscillation Analysis Using Wide Area Voltage Angle Measurements from Frequency Monitoring Network 

LI Bing1, WU Zhen-yue1, LIU Yi-lu2, XIAO Deng-ming1, JIAO Jun-tao1 
1 Department of Electrical Engineering, Shanghai Jiao Tong University, Shanghai 200030, China;
2 Department of Electrical Engineering and Computer Science, University of Tennessee, Knoxville 37901, US
 
 

Abstract: Inter-area oscillation will seriously affect the normal operation of the system. Once the line cascading failure occurs, the system will produce greater disturbance. The inter-area oscillations occurring in the Eastern Interconnection of United States were investigated by six typical cases using the frequency monitoring network (FNET) data. The matrix pencil method of multiple signals was used for the modal analysis. The parameters related to mode shape were calculated. The mode shapes for the dominant mode are revealed for each case. Analysis results depict a view of inter-area mode distribution in the Eastern Interconnection.
            Key words: inter-area oscillation; matrix pencil; mode shape; wide area monitoring system


参考文献
[1] 肖登明,徐欣,刘奕路. 基于Internet 的频率监控网(FNET)[J]. 高电压技术,2001,27(2):39-41.
[2] Klein M, Rogers G J, Kundur P.A fundamental study of inter-area oscillations in power systems[J]. IEEE Transactionson Power Systems,1991,6(3):914-921.
[3] Andersson G, Donalek P, Farmer R, et al.Causes of the 2003 major grid blackouts in North America and Europe, and recommended means to improve system dynamic performance[J].IEEE Transactions on Power Systems,2005,20(4):1922-1928.
[4] 刘振亚. 建设坚强智能电网支撑又好又快发展[J].电网与清洁能源,2009,25(9):1-3.
[5] Phadke A G.Synchronized phasor measurements in power systems[J].IEEE Computer Applications in Power, 1993,6(2):10-15.
[6] Bhargava B, Salazar A.Use of Synchronized Phasor Measurement System for Monitoring Power System Stability and System Dynamics in Real-Time[C]//IEEE Power and Energy Society General Meeting-Conversion and Delivery of Electrical Energy in the 21st Century, 2008.
[7] Cai J Y, Huang Z Y, Hauer J, et al.Current Status and Experience of WAMS Implementation in North America[C]//IEEE/PES Transmission and Distribution Conference and Exhibition:Asia and Pacific, 2005.
[8] Qiu B, Chen L, Centeno V, et al.Internet based frequency monitoring network(FNET)[C]//IEEE Power Engineering Society Winter Meeting, 2001.
[9] Dong J Y, Xia T, Zhang Y C,et al.Monitoring power system disturbances at the distribution level[C]//IEEE Power and Energy Society General Meeting-Conversion and Delivery of Electrical Energy in the 21st Century, 2008.
[10] Zhong Z A, Xu C C, Billian B J, et al.Power system frequency monitoring network(FNET)implementation[J].IEEE Transactions on Power Systems, 2005,20(4):1914-1921.
[11] Crow M L, Singh A.The matrix pencil for power system modal extraction[J].IEEE Transactions on Power Systems, 2005,20(1):501-502.
[12] Ruiz-Vega D, Messina A R, Pavella M. Online Assessment and Control of Transient Oscillations Damping[J].IEEE Transactions on Power Systems,2004,19(2):1038-1047.
[13] Liu G P, Quintero J, Venkatasubramanian V.Oscillation monitoring system based on wide area synchrophasors in power systems[C]//Bulk Power System Dynamics and Control-VII, Revitalizing Operational Reliability, iREP Symposium, 2007.
[14] Trudnowski D J, Johnson J M, Hauer J F.Making Prony analysis more accurate using multiple signals[J].IEEE Transactions on Power Systems,1999,14(1):226-231.