Suzhou Electric Appliance Research Institute
期刊号: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章检索

首页 >> 文章检索 >> 往年索引

1 000 kV特高压同塔双回线路正序参数测试技术

来源:电工电气发布时间:2016-04-06 14:06 浏览次数:32

1 000 kV特高压同塔双回线路正序参数测试技术 

杨靖玮1,王少华2,江宝3,崔竹叶2,李特2 
(1 国网浙江嘉兴供电公司,浙江 嘉兴 314033;2 国网浙江省电力公司电力科学研究院,浙江 杭州
310014;3 国网安徽六安供电公司,安徽 六安 237006)
 
 

摘 要: 输电线路正序参数是电网故障短路电流计算、短路接地故障点位置确定,正常运行时潮流、电压损失计算,及继电保护定值计算等工作的重要基础。提出了1 000 kV 皖电东送特高压同塔双回线路皖南- 浙北段正序参数的测试方法,并进行了现场测试及数据分析。结果表明:采用大容量变频电源和励磁变试验装置,可提高测量信号与干扰信号间的信噪比,降低邻近线路感应电压干扰对特高压线路工频参数测试的影响;采用并联电容补偿法和异频法相结合的综合测试方法,可降低阻抗参数测试时感应电流的影响;皖南- 浙北特高压线路正序参数宜采用异频法得到的测试结果。
关键词: 皖电东送;特高压;同塔双回;工频参数;正序阻抗;正序电容
中图分类号:TM726 文献标识码:B 文章编号:1007-3175(2014)11-0031-05


Positive Sequence Parameter Measurement Technology of 1 000 kV UHV Double-Circuit Transmission Line on Same Tower 

YANG Jing-wei1, WANG Shao-hua2, JIANG Bao3, CUI Zhu-ye2, LI Te2 
(1 State Grid Zhejiang Jiaxing Power Supply Company, Jiaxing 31 4033 , China; 2 State Grid Zhejiang Electric Power Research Institute, Hangzhou 31 0014, China; 3 State Grid Anhui Lu’an Power Supply Company, Lu’an 237006, China) 
 

Abstract: Positive sequence parameters of transmission line are important foundation for short-circuit fault current calculation, shortcircuit ground fault location, power flow and voltage loss calculation, and relay protection setting calculation. Anhui-to-East ultra high voltage (UHV) power transmission line is the first 1 000 kV double-circuit line on the same tower in the world. The measuring method of positive sequence parameters of Wannan-Zhebei transmission line was proposed. The field test was implemented and the test data was analyzed. The results show that the use of large-capacity variable-frequency power source and excitation transformer can improve the signal-to-noise ratio of measuring signal to interfering signal. Then, the influence of interfering voltage induced by adjacent lines on the frequency parameter measurement of UHV transmission line can be reduced. The combined use of parallel capacitance compensation method and non-power frequency method can reduce the influence of the induced current when measuring the impedance parameter. For the positive sequence parameter test of Wannan-Zhebei UHV transmission line, it is appropriate to adopt the test results obtained by non-power frequency method.
          Key words: Anhui-to-East power transmission; ultra high voltage; double-circuit line on same tower; frequency parameter; positive sequence impedance; positive sequence capacitance


参考文献
[1] 刘振亚. 特高压电网[M]. 北京:中国经济出版社,2005.
[2] 刘遵义,卢明,吕中宾,等. 特高压交流输电线路工频参数测量技术及应用[J]. 电网技术,2009,33(10):59-62.
[3] 刘娟,李长益.输电线路工频参数测量时的感应电压影响及消除[J].电力建设,2003,24(8):33-34.
[4] 陈继东,刘晋,吴伯华,等.500 kV 平行线路干扰对工频参数测量影响的研究[J]. 华中电力,2008,21(6):11-14.
[5] 焦阳.输电线路工频参数抗干扰测量方法研究[D].北京:华北电力大学,2005.
[6] 郑钏,蔡金锭.输电线路工频参数影响因素的量化研究[J].高电压技术,2008,34(4):813-815.
[7] 吴湘贵.高压输电线路工频参数抗干扰测量与分析[J].贵州电力技术,2008,32(12):31-32.
[8] 马俊杰,吴伯华.架空输电线路工频参数测量干扰分析及对策[J].华中电力,2010,23(3):6-9.
[9] 杨经超,尹项根,王志华,等. 强干扰环境下输电线路工频参数测试的应用[J]. 电力系统自动化,2008,32(18):67-70.