Suzhou Electric Appliance Research Institute
期刊号: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章检索

首页 >> 文章检索 >> 往年索引

某变电站35 kV电压并列装置烧毁的原因分析

来源:电工电气发布时间:2017-04-21 13:21 浏览次数:13
某变电站35 kV电压并列装置烧毁的原因分析
 
杜严行,叶树平,胡强晖,翟虎成
(国网宁东供电公司,宁夏 银川 750411)
 
    摘 要:针对地区电网中某变电站一起35 kV 电压互感器并列装置烧毁的现象,从电压并列装置的原理出发,结合故障现象,运用戴维南等效电路原理阐述了电力系统铁磁谐振机理,通过分析电磁油浸式电压互感器的原理与内部结构,得出了单相接地及其过程引起的铁磁谐振过电压窜入二次侧回路是导致该电压并列装置两次烧毁的实际原因。给出了消除或抑制电压互感器铁磁谐振的多种应对措施,为今后确保电网安全稳定运行提供参考。
    关键词:铁磁谐振;电压并列装置;烧毁;防范措施
    中图分类号:TM451     文献标识码:B     文章编号:1007-3175(2017)04-0035-05
 
Cause Analysis of 35 kV Voltage Paralleling Device Burning in Certain Substation
 
DU Yan-xing, YE Shu-ping, HU Qiang-hui, ZHAI Hu-cheng
(State Grid Ningdong Power Supply Company, Yinchuan 750411 , China)
 
    Abstract: In allusion to a case of 35 kV voltage transformer burning phenomenon of regional grid substation devices, starting from the principle of the voltage paralleling device and combining with the fault phenomenon, this paper adopted Thevenin equivalent circuit principle to expound the ferromagnetic resonance mechanism of electrical power system. Analysis was made to the principle and interior structure of electromagnetism oil immersed voltage transformer. The one-phase ground was obtained and its process that created ferromagnetic resonance overvoltage plunging into the circuit at secondary side was the actual cause of the voltage paralleling device twice burning. This paper gave a variety of measures to eliminate and suppress the voltage transformer ferromagnetic resonance, which provides references for safe and stable operation of the power grid in future.
    Key words: ferromagnetic resonance; voltage paralleling device; burn; precautionary measure
 
参考文献
[1] 李坚. 电网运行及调度技术问答[M]. 北京:中国电力出版社,2004.
[2] 罗军川.35 kV电容式电压互感器高压熔断器的原因分析[J]. 高压电器,2009,45(3):124-127.
[3] 陈志平, 金向朝.10 kV电磁式电压互感器熔断器频繁烧毁事故分析[J]. 南方电网技术,2009,3(S1):154-157.
[4] 王文洪.10 kV电压互感器的烧毁的原因分析和防范对策[J]. 广东输电与变电技术,2005(6):65-67.
[5] 梅林. 电压互感器并列装置烧毁事故[J]. 电世界,2006,47(3):38.
[6] GB 1207—2006电磁式电压互感器[S].
[7] 要焕年,曹梅月. 电力系统谐振接地[M].2 版. 北京:中国电力出版社,2009.
[8] 武万才,吴志勇,边疆,等. 地区电网电磁式电压互感器烧损和高压熔丝熔断原因分析[J]. 高压电器,2011,47(3):87-92.