一起GIS设备漏气及现场交流耐压试验击穿故障分析

来源:电工电气发布时间:2017-08-23 12:23 浏览次数:7
一起GIS设备漏气及现场交流耐压试验击穿故障分析
 
胡全义,秘立鹏,刘天奇,张欣伟
(国网内蒙古东部电力有限公司电力科学研究院,内蒙古 呼和浩特 010020)
 
    摘 要:针对某220 kV 变电站66 kV 气体绝缘金属封闭组合电器(GIS) 因盆式绝缘子出现裂痕发生漏气事件,介绍了设备漏气故障点发现过程,解体处理后进行主回路绝缘试验过程中出现击穿现象,通过闪络定位仪准确定位到击穿气室,再次解体发现导电座上有明显的磕碰痕迹,改变了导电座周围的空间电场分布,导致在耐压过程中导电座下侧局部电场发生畸变,耐压过程中最终在绝缘子表面发生了沿面闪络放电。试验验证了闪络定位仪在闪络故障检测及故障点定位应用中的准确性和有效性,可在高压设备交接试验中推广。
    关键词:GIS;盆式绝缘子;SF6 气体泄漏;交流耐压;定位
    中图分类号:TM595     文献标识码:B      文章编号:1007-3175(2017)08-0043-04
 
A Case of Insulated Swithgear Equipment Air Leakage and Site AC Withstand Voltage Test Breakdown Fault Analysis
 
HU Quan-yi, MI Li-peng, LIU Tian-qi, ZHANG Xin-wei
(State Grid East Inner Mongolia Electric Power Company Research Institute, Hohhot 010020, China)
 
    Abstract: In allusion to the leakage event of basin-type insulator cracks in the 66 kV gas insulated switchgear (GIS) in the 220 kV substation, introduction was made to the discovery process of equipment air leakage fault points and the punchthrough in the process of major loop insulation test after disintegration disposal. The flashover position indicator was used to carry out accurate positioning to the breakdown air chamber. There were obvious signs of bumps on the conductive seat, which changed the space electric field around the conductive seats and caused electric field distortion in the process of withstand voltage downside the conductive seat. In the process of withstand voltage the flashover discharged along surface of the insulators finally. The test verifies the accuracy and validity of the flashover position indicator applied in the flashover faults testing and positioning.
    Key words: gas insulated switchgear; basin-type insulator; SF6 leakage; AC withstand voltage; positioning
 
参考文献
[1] 姜敏,杨卫东,乔朝霞. 气体绝缘组合电器局部放电分析[J]. 山西电力,2011(4):28-29.
[2] 李秀卫,王庆玉,毛惠卿,等. 一起组合电器内部绝缘故障综合分析[J]. 高压电器,2012,48(8):99-102.
[3] 黄纯德,田赟,冀晋川.220 kV 变电站组合电器盆式绝缘子开裂分析[J]. 山西电力,2013(4):26-28.
[4] 陈昱同,郭建宏,刘杨,等.220 kV某GIS盆式绝缘子漏气原因分析及处理措施[J]. 高压电器,2015,51(12):196-200.
[5] 赵畹君. 高压直流输电工程技术[M]. 北京:中国电力出版社,2011.
[6] 沈宏强,葛占雨. GIS交流耐压试验及其对发现内部异常情况的作用[J]. 安装,2013(S1):62-64.
[7] 崔巨勇,杨鹤,韦德福,等. GIS现场闪络故障定位关键技术应用[J]. 东北电力技术,2016,37(8):59-62.
[8] 高立超,孙兴彬,杨志华,等.330 kV GIS设备现场交流耐压试验击穿故障分析[J]. 电气技术,2016,17(8):86-88.
[9] 曲文韬,黄锐,吕俊涛.220 kV GIS设备漏气原因分析及预防措施[J]. 电力科学与工程,2013,29(8):21-26.
[10] 刘旭.220 kV GIS设备交流耐压击穿故障简析[J].安徽电力,2012,29(3):5-7.